- Fast shipping from four branches
- 30-day returns on unopened products
The Kidde EWGVMWN is an outdoor-rated Genesis EWG wall strobe built for NAC circuits that need weather-resistant visual notification without an audible component. Multi-candela output (15-115cd, field-selectable) delivers code-compliant coverage across a range of mounting distances, and the IP66/NEMA 4X enclosure handles exposed installations where indoor-rated devices can't.
Built for the commercial installer
The EWG strobe mounts directly to a standard 4-inch square electrical box - no proprietary backplates or adapter brackets. The outdoor-rated housing carries IP66 and NEMA 3R/4/4X ratings with an operating range of -40F to 151F, covering loading docks, parking structures, covered walkways, and exterior egress paths. UL 1638, UL 1971, and ULC-S526 listed. White housing with no marking - deploy where audible notification is already handled by a separate device on the circuit, or where visual-only signaling meets the AHJ's requirements.
Key features
- Multi-candela field selection (15-115cd): adjust output to match the coverage area without swapping the device
- IP66, NEMA 3R/4/4X rated: handles rain, dust, hose-down, and temperature extremes from -40F to 151F
- Standard 4" square box mount: no special hardware, no adapter plates
- Low current draw: maximizes device count per NAC circuit
- White housing, unmarked: blends into commercial and industrial exterior finishes without "FIRE" marking restrictions
- UL 1638, UL 1971, ULC-S526 listed: meets commercial fire alarm notification standards for outdoor applications
System requirements
Connects to any fire alarm control panel (FACP) NAC circuit providing 12-33V DC or FWR. For SLC-connected addressable systems, pair with the appropriate monitor/control module per the panel manufacturer's wiring guide.
Specifications
| SKU | KD-EWGVMWN |
|---|---|
| Brand | Kidde Commercial |
| Form factor | Wall mount outdoor strobe, Genesis EWG series |
| Strobe output | Multi-candela, 15-115cd field-selectable |
| Power input | 12-33V DC or FWR (from NAC circuit) |
| Weather rating | IP66, NEMA 3R/4/4X |
| Operating temp | -40°F to 151°F (-40°C to 66°C) |
| Mounting | Standard 4" square electrical box |
| Housing color | White |
| Marking | Unmarked (no "FIRE" text) |
| Compliance | UL 1638, UL 1971, ULC-S526 |