- Fast shipping from four branches
- 30-day returns on unopened products
The EWGVRF gives a fire alarm zone visual-only signaling in a weatherproof, FIRE-marked housing, for jobs that already have audio covered and just need the strobe.
Built for the commercial fire installer
High-performance LED strobe technology draws less current than legacy Xenon strobes, so more devices fit on a circuit with lower-gauge wire and fewer booster power supplies - and it's backward-compatible enough to mix on the same circuit as older Xenon strobes during a retrofit. Field-selectable 15 or 30 cd output draws the same current at either setting.
Key features
- NEMA 4X / IP66 listed for outdoor wet applications; IP67 compliant standalone
- Field-selectable 15 or 30 cd strobe output, same current draw at either setting
- Operating range -40°F to 151°F (-40°C to 66°C)
- Quick-swap cover - change FIRE/ALERT/no marking without replacing the device
System requirements
Flush mount: 4-inch-square-deep box with EWGRMA adapter plate (red, sold separately). Surface mount: Model 449 (gray) or 74347U (red) weatherproof box with adapter plate and ring. DC operating voltage only.
Specifications
| SKU | KD-EWGVRF |
|---|---|
| Brand | Kidde Commercial |
| Form factor | Outdoor-rated wall/ceiling strobe only, red, FIRE marking |
| Strobe output | Field-selectable 15 or 30 cd (UL 1971 indoor) |
| Operating voltage | 16-33 Vdc (DC only) |
| Operating environment | -40°F to 150.8°F (-40°C to 66°C), 0-95% RH noncondensing |
| Mounting | Flush: 4" square box + EWGRMA adapter; Surface: 449 or 74347U box + adapter and ring |
| Compliance | NEMA 4X, IP66 (installed), IP67 (standalone), UL/ULC |