The INT-7AT is a wall-mount temporal horn-strobe built for straightforward two-wire fire alarm circuits. It runs on 16 to 33 Vdc, self-synchronizes with other Integrity devices on the same circuit without an external control module, and mounts to a standard North American two-gang box with a single screw.
Built for the commercial fire installer
The strobe is rated 15 cd wall / 15 cd ceiling per UL 1971 and up to 75 cd (UL 1638) depending on orientation and switch setting, and the horn is field-configurable for temporal or steady tone at high (98 dBA) or low (94 dBA) output. Terminals accept up to #12 AWG for polarized, diode-supervised connections, and the red Noryl housing holds up in industrial and high-traffic areas. Fully compatible with Genesis signals on the same circuit.
Key features
- Self-synchronizing: strobe and horn sync with other Integrity devices on a common circuit, no control module required
- Field-configurable output: temporal or steady tone, high (98 dBA) or low (94 dBA)
- 15/75 cd strobe rating (UL 1971/1638), suitable for public and private mode signaling
- Single-screw mounting plate: wire it, hang it for inspection, then fasten to the box
- Genesis-compatible for mixed-signal circuits
System requirements
Flush mounts to a standard North American two-gang electrical box (2-1/2" minimum). Requires a constant (not pulsed) 16 to 33 Vdc signal circuit. For outdoor use, install in an INT-WB weatherproof box.
Does this horn-strobe need an external sync module?
Can I use this in a sleeping room?
Is this suitable for outdoor installation?
What box does this mount to?
Spec Sheet