The Kidde 1509-AQN5 is a completely flush-mounted electromagnetic door holder built for fire-rated commercial doors. It mounts on a standard single-gang outlet box with concealed wiring, leaving a clean profile that blends into the wall. Multi-voltage operation (24 VAC, 24 VDC, or 120 VAC) means it connects to whatever power source the panel delivers - no external transformer required in most installs.
Built for the commercial installer
Fail-safe design releases the door on power loss, meeting fire code requirements without additional relay logic. The self-contained unit has no moving parts and requires no maintenance after install. UL and ULC listed (R6291) for fire protective signaling systems.
Key features
- Completely flush wall mount: concealed wiring on a standard single-gang box for a clean, low-profile installation
- Multi-voltage operation: 24 VAC, 24 VDC, or 120 VAC at just 0.015A draw
- 25 lb (111N) holding force with adjustable swivel contact plate and shock-absorbing nylon ball
- Fail-safe release: door releases on power loss for fire code compliance
- Self-contained, no moving parts: zero maintenance after installation
- UL and ULC listed (R6291) for fire protective signaling systems
System requirements
Requires a standard single-gang (2 x 4 inch) outlet box for flush mounting. Compatible with any FACP or NAC circuit that provides 24 VAC, 24 VDC, or 120 VAC. Replacement armature available as CS2595-5.