- Fast shipping from four branches
- 30-day returns on unopened products
The WG4WN-SVMA covers voice notification and visual signaling in one weatherproof device, with an amber lens that visually separates mass notification alerts from red-lens fire alarm signals on the same site.
Built for the commercial fire installer
Field-selectable speaker taps (1/4, 1/2, 1, or 2 watt) and voltage (25V or 70V) let one part number cover most audio circuit designs, and the strobe's four standard-output candela settings are set the same way - remove the cover and slide a switch, no separate model needed per candela rating. Settings stay visible after the cover goes back on through a sealed viewport. The full backplane sealing gasket allows installation to recessed in-the-pour boxes as well as surface boxes on raceways, and the shallow, low-profile housing rejects the elements down to -31°F.
Key features
- Field-selectable speaker wattage (1/4, 1/2, 1, 2W) and voltage (25V/70V)
- Field-selectable amber strobe candela - 4 settings without swapping devices
- Amber lens visually distinguishes ECS/MNS alerts from fire alarm signaling
- Rated -31°F to 151°F, indoor or outdoor
- Wall or ceiling mount, strobe positionable above, below, or to either side
- UL 1971/1638 synchronization compatible with Genesis and Integrity signals on the same circuit
System requirements
Wet locations require a Kidde 74347U outdoor-rated box; dry locations use a standard 4-inch square by 1-1/2-inch deep box (2-1/8-inch deep if using the optional WG4WTS trim skirt). Strobe synchronization requires a compatible control module (VM/VS/FX Series panels or GSA-CC1S/SIGA-CC2A-family modules).
Specifications
| SKU | KD-WG4WN-SVMA |
|---|---|
| Brand | Kidde Commercial |
| Form factor | Outdoor-rated wall/ceiling speaker-strobe, white, no marking |
| Strobe output | Standard output, amber: 13/25/59/62 cd indoor (UL 1971 equivalent) |
| Lens color | Amber |
| Speaker circuit | 25 VRMS or 70 VRMS, switch-selectable; 1/4, 1/2, 1, or 2W taps |
| Speaker output | 80.8 to 90.0 dBA depending on tap |
| Strobe circuit | 24 Vdc / 24 VFWR nominal |
| Operating environment | -31°F to 151°F (-35°C to 66°C), 0-95% RH noncondensing |
| Wire size | 12 to 18 AWG |
| Mounting | Wet: Kidde 74347U box; Dry: 4" square x 1-1/2" deep box (2-1/8" with trim skirt) |