Kidde Commercial

Universal Class A/B Module. Select From 15 Personality Codes Including Class A Or B Initiating Circuits Class A Or B Signaling Circuits

SKU KD-GSA-UM

  • Fast shipping from four branches
  • 30-day returns on unopened products

The GSA-UM is a Signature Series intelligent module that takes on whatever interface duty a job calls for, from pull stations to waterflow switches to a dry relay contact, all from the same stocked part. The installer selects the function by downloading one of 15 personality codes from the loop controller, so the field decision doesn't require carrying a dozen different module types on the truck.

Built for the commercial fire installer

Mounted to a standard North American 2-gang box, the GSA-UM connects two Class B or one Class A initiating device circuit, a Class A/B notification appliance circuit, a 2-wire smoke detector circuit, or a Form C dry relay contact, depending on the code selected. Kidde's ground fault detection pinpoints the specific module with the wiring fault, cutting troubleshooting time on a job with dozens of modules on the loop. Compatible with Kidde VM and VS Series control panels.

Key features

  • 15 selectable personality codes cover IDC, NAC, 2-wire smoke, and relay applications from one part number
  • Ground fault detection by address pinpoints the exact module with the fault, not just the loop
  • Electronic addressing: no dials or switches, address is downloaded from the loop controller or SIGA-PRO tool
  • Stand-alone operation: continues making alarm decisions if loop controller polling stops
  • No twisted or shielded wire required on retrofit jobs from conventional to Signature Series

System requirements

Requires a Kidde Signature Series loop controller on VM or VS Series control panels. Mounts to a North American 2-1/2" deep 2-gang box or a 4" square box with a 2-gang cover and GSA-MP mounting plate.

Specifications

SKUKD-GSA-UM
BrandKidde Commercial
Form factorStandard 2-gang mount, intelligent addressable module
Personality codes15 selectable codes: Class A/B IDC, NAC, 2-wire smoke, and Form C relay applications
Operating voltage15.2 to 19.95 Vdc (19 Vdc nominal)
Address requirementsTwo module addresses, electronically assigned
Wiring terminations#12 to #18 AWG (2.5 mm² to 0.75 mm²)
MountingNorth American 2-1/2" deep 2-gang box, or 4" square box with GSA-MP mounting plate
Operating temp32°F to 120°F (0°C to 49°C)
Storage temp-4°F to 140°F (-20°C to 60°C)
CompatibilityKidde VM and VS Series (Signature Series) control panels
Shipping weight0.5 lbs (0.23 kg)
ComplianceUL, ULC, MEA, CSFM

Documents and resources

FAQs

What can this module be configured to do?
Depending on the personality code selected, it connects two Class B or one Class A initiating circuit, a Class A/B notification appliance circuit, a 2-wire smoke detector circuit, or a Form C dry relay contact.
Do I need to set an address with dials or switches?
No. The loop controller electronically addresses the module and stores its serial number in memory. No mechanical address switches to set.
What happens if the loop controller stops polling?
The module continues to make alarm decisions in standalone mode using its on-board microprocessor, until communication resumes.
What panels is this compatible with?
Kidde VM and VS Series (Signature Series) control panels with a Signature loop controller.