The INT-7AS combines a mylar-cone speaker with a 15/75 cd strobe in one wall-mounted appliance, covering audible and visual notification for a zone on a 70V audio circuit without stacking two separate devices on the box.
Built for the commercial fire installer
The sealed-back speaker construction improves durability and audibility, with wattage taps from 1/4W to 2W for on-site flexibility across zone sizes. The strobe exceeds UL 1971 synchronization requirements (within 10 milliseconds over two hours) when paired with a compatible sync source, and is fully compatible with Genesis strobes on the same circuit. A single-screw mounting plate speeds installation - no separate trim plate required.
Key features
- Sealed-back mylar speaker with wattage taps from 1/4W to 2W
- 70 VRMS speaker circuit
- 15/75 cd strobe, UL 1971 and UL 1638 listed for public and private mode
- Genesis-compatible synchronization with an external control module
- Field-changeable lens markings via optional LKW/LKC kits
System requirements
Speaker circuit: 70 VRMS. Strobe circuit: 16-33 Vdc continuous (constant, not pulsed). Strobe synchronization requires a compatible control module (VM/VS/FX Series panels or GSA-CC1S/SIGA-CC2A-family modules).