The FX-IDCWS connects two normally-open initiating device circuits to a Kidde FX Series fire alarm control panel on a single SLC address pair - one waterflow alarm circuit and one supervisory circuit. Rotary TENS and ONES dials set the address on-site with no programming tool required, and the compact footprint fits standard 4-inch electrical boxes.
Built for the commercial fire alarm installer
Each module requires two consecutive addresses on the SLC loop and monitors both circuits independently. A waterflow switch activation reports as an alarm condition, while a supervisory switch activation reports as a supervisory condition. Class B circuit operation with 47 k EOL supervision keeps wiring straightforward. Compatible with Kidde FX Series intelligent analog addressable fire alarm control panels. UL and ULC listed.
Key features
- Dual IDC monitoring on one module: waterflow alarm and supervisory circuits share a single device, reducing panel point count and box fill
- Rotary address dials: set TENS and ONES on-site without a laptop or programming tool
- Standard box mounting: fits 4-inch square boxes (1-1/2" or 2-1/2" deep) and 2-gang boxes
- Low SLC loop load: 550 A standby, 725 A activated - leaves headroom on longer loops
- Wide operating range: 32F to 120F at up to 93% RH, suitable for mechanical rooms and riser closets
System requirements
Requires a Kidde FX Series analog addressable fire alarm control panel and connection to an SLC loop. Each module occupies two consecutive addresses. Wire with 12-18 AWG conductors, max 50 circuit resistance. Supervised with 47 k EOL resistor (P/N: EOL-47, ordered separately).
Specifications
| SKU | KD-FX-IDCWS |
|---|---|
| Brand | Kidde Commercial |
| Form factor | Addressable SLC module, mounts in 4" square box |
| Communication | SLC (Signaling Line Circuit) to Kidde FX Series FACP |
| Power input | SLC loop powered, max 20V peak-to-peak |
| Current draw | Standby 550 μA, Activated 725 μA |
| Circuit type | Class B, dual IDC (waterflow + supervisory) |
| EOL resistor | 47 kΩ (P/N: EOL-47) |
| Addressing | Rotary dial, two consecutive addresses required |
| Address range | 01-63 (64 point) or 01-126 (1000 point) |
| Wire size | 12, 14, 16, or 18 AWG |
| Max circuit resistance | 50 Ω (25 Ω per wire) |
| Max circuit capacitance | 0.1 μF |
| Operating temp | 32°F to 120°F (0°C to 49°C) |
| Operating humidity | 0 to 93% RH, non-condensing |
| Storage temp | -4°F to 140°F (-20°C to 60°C) |
| Ground fault impedance | 10 kΩ |
| Compatible electrical boxes | 4" square x 2-1/2" deep, 4" square x 1-1/2" deep, 2-gang box |
| Ship weight | 0.50 lbs (0.23 kg) |
| Compliance | UL, ULC listed |