The Kidde GSA-CC2 is an analog addressable dual input riser module that selects between two signal or audio input circuits and routes the active circuit to a single signal output. Powered directly from the SLC (signaling line circuit), it drops into Kidde FX Series intelligent fire alarm systems with rotary addressing and no external power supply required at the module.
Built for the commercial fire installer
Circuit switching on a riser shouldn't require a custom wiring solution. The GSA-CC2 handles the selection between two input circuits at the module level, keeping riser configurations clean and field-serviceable. Rotary dials set the SLC address without a programming tool at the device, and a bicolor LED (green normal, red active) gives visible confirmation of module state during commissioning and service calls. Ground fault detection at the module pinpoints wiring issues to the specific device, saving troubleshooting time across long SLC runs.
Key features
- Dual input circuit selection: switches between two signal or audio input circuits to one signal output - clean riser management without external switching hardware
- SLC powered: draws power from the signaling line circuit, no separate power supply or additional wiring at the module
- Rotary addressing: set device address with two screwdriver-adjustable dials - no special tools or programming steps required at the device
- Ground fault detection: isolates wiring faults to the individual module, cutting troubleshooting time on the SLC loop
- Standard box mounting: fits North American 4-inch square boxes (2-1/2 in. deep two-gang or 1-1/2 in. deep standard), same as the full Kidde FX module family
- Bicolor LED status indicator: flashing green for normal operation, flashing red when active - visible at a glance during commissioning
System requirements
Requires a Kidde FX Series intelligent fire alarm control panel. Connects to the SLC and is powered by the communication line. Wire per NFPA 72 and CAN/ULC-S524 standards using 12, 14, 16, or 18 AWG conductors.
What panel does the GSA-CC2 require?
What does the GSA-CC2 do?
How is the device address set?
What electrical box does this mount in?
Does the GSA-CC2 need a separate power supply?
What wire gauge is required?
Spec Sheet