The FX-10R is a ten-zone conventional fire alarm control panel built for the small and mid-size commercial jobs that do not justify an addressable system. Ten Class B initiating device circuits and four Class B notification appliance circuits come standard, and pairs of each convert to single Class A circuits in the field, so one part number covers a wide range of survivability requirements without a re-order.
Built for the commercial fire installer
The 7.0 amp NAC power supply is the reason this panel gets specified. Two amps per circuit across four circuits means most buildings get their horn-strobes off the panel itself with no booster to mount, wire, and supervise. The cabinet charges up to two 24 Ah sealed lead acid batteries, with 18 Ah fitting inside the enclosure, so standby calculations rarely force you into an external battery cabinet.
Zone and NAC circuits are labelled on the front panel behind the door, so a technician reading the annunciator sees what tripped without pulling drawings. Listed under UL 864 (S3000), ULC-S527, CSFM, and FDNY.
Key features
- Ten Class B IDCs, field-convertible to Class A: pairs convert to single Class A circuits, giving combinations from 10 Class B down to 5 Class A
- Four Class B NACs with 7.0A total power: 2.0 amps per circuit, enough to drive most notification loads without a booster
- On-board battery charging to 24 Ah: up to two batteries, 18 Ah inside the cabinet, for extended standby without an external enclosure
- Three Form C contacts: separate alarm, trouble, and supervisory outputs rated 30 Vdc at 1 A for interface to building systems
- Resettable auxiliary output: 0.5 amps of regulated 24 Vdc, programmable as resettable for four-wire detection
- Walk test and lamp test from the front panel: one-person acceptance testing without a second technician at the panel
- Semi-flush or surface mount: the F-TRIM10R trim ring finishes a semi-flush installation
System requirements
Requires a dedicated 120 Vac 60 Hz branch circuit at 2.2 amps. Terminals accept 18 to 12 AWG. Two sealed lead acid batteries are ordered separately and are required for standby. For remote annunciation, add an FSRA10 or FSRA10C. Consult detector compatibility list 3101019-EN for the maximum number of detectors per initiating circuit. If a DACT is required for central station reporting, order the FX-10RD, which adds an upload/download DACT and modem in the same enclosure.
Specifications
| SKU | KD-FX-10R |
|---|---|
| Brand | Kidde Commercial |
| Form factor | Wall-mount steel enclosure, 30 x 15.0 x 3.75 in (76.2 x 38.1 x 9.5 cm) |
| Panel type | Conventional fire alarm control panel, 10 zone |
| Initiating device circuits | 10 Class B, convertible in pairs to Class A (10B/0A through 0B/5A) |
| Notification appliance circuits | 4 Class B, convertible in pairs to Class A (4B/0A, 2B/1A, 0B/2A) |
| NAC power | 7.0 amps total, 2.0 amps maximum per circuit |
| NAC voltage rating | 24 Vfwr |
| Power input | 120 VAC, 60 Hz, 2.2 amps |
| Power supply | 7.5 amps total |
| Auxiliary output | 24 VDC regulated, 0.5 amps max, programmable as resettable |
| Battery capacity | Up to two 24 Ah sealed lead acid; 18 Ah maximum inside the cabinet |
| Panel current draw | Standby 128 mA, alarm 242 mA |
| IDC operating voltage | 16.9 to 29 VDC |
| IDC alarm current | 3.0 mA |
| IDC circuit limits | Maximum loop resistance 26 ohms, maximum loop capacitance 0.03 uF |
| UL detector ID | 100 |
| Alarm contact | Form C, normally open, 30 VDC @ 1 A resistive |
| Trouble contact | Form C, 30 VDC @ 1 A resistive |
| Supervisory contact | Form C, normally open, 30 VDC @ 1 A resistive |
| Terminal wire gauge | 18 to 12 AWG (0.75 to 2.5 sq mm) |
| Operating temp | 32 to 120 F (0 to 49 C) |
| Operating humidity | 5 to 93% RH, non-condensing |
| Agency listings | UL 864 (S3000), ULC-S527, CSFM, FDNY |
| Shipping weight | 30.5 lb (13.8 kg) |