Kidde Commercial

SuperDuct Four-Wire Duct Smoke Detector, Controller with Sensor, RJ45

SKU KD-SD-4WJ

  • Fast shipping from four branches
  • 30-day returns on unopened products

The SD-4WJ pairs a SuperDuct controller and sensor in one RJ45-ready package, dropping into ductwork under 2 inches deep and giving an installer everything needed for a single-airstream install without ordering the controller and sensor separately.

Built for the commercial fire installer

Patented differential sensing checks the environment every eight minutes and automatically compensates for dirt and humidity, cutting the sensitivity drift that drives nuisance duct alarms on other detectors. The magnet-activated test/dirty/reset switch works through the closed clear cover, so routine testing and troubleshooting never require opening the housing. One controller supports up to two detectors, and up to 15 controllers can interconnect for multi-fan shutdown on larger air handling jobs.

Key features

  • Under 2 in deep - drops into tight duct spaces other detectors can't reach
  • Self-compensating sensing: checks for dirt and humidity every 8 minutes and adjusts automatically
  • Test without opening the cover: magnet-activated test/dirty/reset switch
  • RJ45 interconnection for fast drop-in migration from other detectors
  • One controller, two detectors: supports remote or tandem-mounted sensor
  • Multi-fan shutdown: interconnect up to 15 controllers

System requirements

Air velocity rating 100 to 4,000 ft/min. Operates on 24 Vdc, 24 Vac, 120 Vac, or 230 Vac. Order an air sampling tube separately to match duct size; RJ45 wiring harnesses (5, 10, or 15 ft) available for remote-mounted sensors.

Specifications

SKUKD-SD-4WJ
BrandKidde Commercial
Form factorController with sensor (RJ45), tandem or remote mount
Detection methodPhotoelectric, with differential environmental compensation
Air velocity rating100 to 4,000 ft/min
Sensitivity0.67 to 2.46% obscuration/ft
Operating voltage24 Vdc, 24 Vac, 120 Vac, or 230 Vac
Operating temp-4°F to 158°F (-20°C to 70°C)
Relays1 alarm (2.0A @ 30 Vdc), 1 trouble (2.0A @ 30 Vdc), 2 auxiliary (10A @ 30 Vdc / 250 Vac)
Wiring distanceDetector to controller: 100 ft max; controller interconnect: up to 1,976 ft on 14 AWG
Dimensions14.51 x 5.45 x 1.90 in (controller and detector, tandem-mounted)
ComplianceUL, ULC, CSFM, FM, MEA

Documents and resources

FAQs

Does the SD-4WJ include the air sampling tube?
No. The included exhaust tube is provided, but the air sampling tube is ordered separately (available in 8 to 120 inch lengths) to match the duct.
Can the sensor be mounted away from the controller?
Yes. One or both sensors can be installed remotely from the controller using an RJ45 wiring harness, available in 5, 10, or 15 ft lengths.
How is the detector tested?
With the included magnet-activated test/dirty/reset switch, or from a remote SD-TRM4 (magnetic) or SD-TRK4 (keyed) Remote Test/Reset Station, without opening the detector cover.
Can one controller support two detectors?
Yes. Each SD-4WJ controller supports up to two sensors, tandem-mounted or remote.