The FX-1000 drops into mid-sized commercial projects as a four-loop intelligent addressable fire alarm control panel with room to scale. Ships with one 250-point SLC loop installed and expands to four loops and 1,000 addressable points without swapping the panel - right-size the system at install and add capacity as the building grows.
Built for the commercial fire alarm installer
Four onboard Class B (Style Y) NAC circuits rated at 6.0 A FWR total reduce the need for external booster power supplies on typical jobs. The panel accepts Class A or Class B SLC wiring (Styles 4, 6, 7) and supports up to 32 input zones and 8 remote annunciator drops over RS-485 with a 4,000 ft. data line. Primary power is 120 VAC (or 230 VAC, 50-60 Hz) with 24 VDC sealed lead-acid battery backup - up to two 18 Ah batteries fit inside the cabinet for 24- or 60-hour standby. UL 864 and ULC-S527 listed.
Key features
- Scalable four-loop architecture: starts with one 250-point loop, expands to 1,000 addressable points across four SLC loops
- Four onboard NACs: 6.0 A FWR total at 120/230 VAC, 2.5 A per circuit - reduces external power supply requirements
- Class A or Class B SLC wiring: Styles 4, 6, and 7 for flexible riser design
- 32 input zones and 8 remote annunciator drops over RS-485 (up to 4,000 ft. data line length)
- Built-in battery backup: accepts up to two 18 Ah sealed lead-acid batteries inside the red surface-mount cabinet
- UL 864 and ULC-S527 listed for code-compliant commercial fire alarm installations
System requirements
Primary power: 120 VAC, 60 Hz (or 230 VAC, 50-60 Hz). Off-premises communications require an SA-DACT2 dialer or KCG1 cellular gateway, ordered separately. Expansion beyond one SLC loop requires FX-SLC1 or FX-SLC2 expansion modules. Compatible with Kidde Intelligent FX series detectors and modules.
Specifications
| SKU | KD-FX-1000 |
|---|---|
| Brand | Kidde Commercial |
| Form factor | Surface-mount cabinet, red door |
| SLC loops | 1 installed, expandable to 4 (Class A or B, Styles 4, 6, 7) |
| Addressable points | Up to 1,000 (250 per loop) |
| NAC circuits | 4 Class B (Style Y) or 2 Class A (Style Z), 6.0 A FWR total, 2.5 A per circuit max. |
| Power input | 120 VAC, 60 Hz, 2.0 A max. / 230 VAC, 50-60 Hz, 0.97 A max. |
| Operating voltage | 24 VDC |
| Auxiliary power output | Aux 1: 500 mA, 24 VDC / Aux 2: 500 mA, 24 VDC |
| Base panel standby current | 172 mA |
| Base panel alarm current | 267 mA |
| Input zones | 32 max. |
| Remote annunciator | 8 drops max., RS-485 Class A or B, 4,000 ft. data line |
| Max loop resistance | 66 Ω |
| Max loop capacitance | 0.5 µF |
| Battery | Sealed lead acid, 24 VDC, up to two 18 Ah in cabinet (26 Ah max.) |
| Battery standby | 24 hour or 60 hour |
| Operating temp | 32°F to 120°F (0°C to 49°C) |
| Operating humidity | 0 to 93% noncondensing |
| Terminal rating | 12 to 18 AWG (0.75 to 2.5 mm²) |
| Alarm contact | Form C N.O., 24 VDC at 1 A (resistive load) |
| Trouble contact | Form C, 24 VDC at 1 A (resistive load) |
| Supervisory contact | Form A N.O., 24 VDC at 1 A (resistive load) |
| Compliance | UL 864, ULC-S527 |