The Kidde 302-AW-194 is an all-weather rate compensation heat detector rated at 194F (90C), built for environments where standard detectors won't survive - outdoor covered areas, parking garages, cold storage, and anywhere moisture, condensation, or corrosive atmospheres are a factor. Hermetically sealed and tamperproof, it mounts vertically and self-restores after activation with no manual reset needed.
Built for the commercial fire installer
Rate compensation technology offsets the thermal lag that plagues conventional fixed-temperature detectors, giving you faster response on rapid fires without false alarms from gradual temperature changes. The 302-AW handles minimum ambient temperatures down to -40F and maximum ceiling temperatures up to 150F. FM Approved and UL Listed (UL 521), it fits directly into conventional fire alarm panel circuits with two-wire normally-open contacts.
Key features
- Rate compensation detection: offsets thermal lag for faster response to real fires while rejecting slow temperature swings
- All-weather construction: hermetically sealed, corrosion resistant, rated for environments with moisture, condensation, and explosive atmospheres
- Self-restoring operation: resets automatically when temperature drops below the rated threshold - no manual reset, no truck roll
- Wide ambient range: operates from -40F to 150F ceiling temperature, covering cold storage to industrial environments
- FM Approved and UL Listed: meets code requirements for commercial fire alarm installations
- Simple two-wire connection: normally-open contacts wire directly to any conventional FACP initiating circuit
System requirements
Connects to any conventional fire alarm control panel via two-wire normally-open initiating circuit. Rated for 6-125 VAC (5A), 6-25 VDC (1A), or 125 VDC (0.5A). Refer to NFPA 72 for detector spacing and placement requirements.
Specifications
| SKU | KD-302-AW-194 |
|---|---|
| Brand | Kidde Commercial |
| Form factor | All-weather rate compensation heat detector, vertical mount |
| Detection method | Rate compensation with differential air chamber |
| Rated temperature | 194°F (90°C) |
| Contact type | Normally open, fine silver contacts |
| Electrical rating (VAC) | 6-125 VAC, 5A |
| Electrical rating (VDC) | 6-25 VDC / 1A, 125 VDC / 0.5A |
| Operating temp | -40°F to 150°F (-40°C to 66°C) ambient/ceiling |
| Construction | 0.040 anodized aluminum sensing shell, hermetically sealed, tamperproof |
| UL spacing (vertical) | 50' x 50' (15.2 x 15.2 m) |
| UL spacing (horizontal) | 40' x 40' (12.2 x 12.2 m) |
| FM spacing | 30' x 30' (9.1 x 9.1 m) |
| Compliance | FM Approved, UL Listed, MEA |