The K-RLCD mounts to a standard 4-inch square electrical box and gives fire alarm installers remote status visibility on Kidde Commercial EVOLVE, FX64, FX1000, VS1, VS4, and VM panels - without pulling the FACP door open. The 4-line by 20-character backlit LCD displays system status in plain English, while dedicated LEDs confirm Power, Fire Alarm, Supervisory, Ground Fault, and Trouble conditions at a glance.
Built for the commercial fire alarm installer
RS-485 communication supports Class A or Class B wiring with runs up to 4,000 ft. Set the DIP switch address and the annunciator pulls all zone and system data from the panel automatically - no programming required. This is the model without common controls, so there's no Reset, Signal Silence, or Drill button on the faceplate. Ack/Silence and Lamp Test are included. If the job calls for full common controls, look at the K-RLCD-C.
Key features
- Large backlit LCD display: 4 lines of 20 characters each for clear, readable system status from across the lobby
- Zero programming: set the RS-485 address via DIP switch and the unit auto-populates from the FACP
- Flexible wiring: Class A or Class B RS-485 on 18-14 AWG twisted pair, up to 4,000 ft. wire runs
- Standard 4-inch box mount: flush-mount to any North American 4-inch square electrical box, or surface-mount in optional RA-ENC enclosures
- Status LEDs and internal buzzer: Power, Fire Alarm, Supervisory, Ground Fault, Trouble, and Controls Enabled indicators standard
- UL, ULC, and FM listed for code-compliant commercial fire alarm installations
Panel compatibility
Compatible with Kidde Commercial FX64, FX1000, VS1, VS4, EVOLVE, and VM fire alarm control panels. Up to two K-RLED24-2 LED zone expanders can be daisy-chained for zone-level annunciation alongside the LCD display.
What is the difference between the K-RLCD and K-RLCD-C?
Does this annunciator require programming?
How far can the annunciator be from the panel?
Can I add zone LED annunciation alongside the LCD display?
What enclosures are available for the R-Series annunciators?
Which Kidde fire alarm panels are compatible?
Spec Sheet