The Genesis ceiling speaker-strobe puts voice notification and visual alerting on a single device for mass notification systems. Field-selectable candela settings and multiple speaker power taps let you match output to the space without swapping hardware - one device covers corridors, open offices, and assembly areas.
Built for the commercial installer
Mounts on standard 4-inch square boxes with a plaster ring or 2-gang boxes - same rough-in as conventional ceiling notification appliances. The optional room-side wiring plate (GRSW, sold separately) keeps 12-18 AWG terminations accessible after ceiling finish is in place. White housing with red ALERT text and amber lens meets mass notification marking requirements.
Key features
- Field-selectable candela: four amber-lens settings (13/26/65/82 cd) configurable on site without stocking multiple models
- Dual-voltage speaker: 25V/70V with four power taps (1/4W, 1/2W, 1W, 2W) delivering up to 90 dBA
- ALERT marking with amber lens: white housing with red ALERT text for mass notification code compliance
- Standard box mounting: fits 4-inch square with plaster ring or 2-gang boxes, no special hardware
- Room-side wiring: optional GRSW plate keeps wire terminations accessible below the finished ceiling
- Listed and approved: UL 1638, UL 1971 (mass notification), ULC, CSFM, FM Approved, ADA compliant
System requirements
Requires a fire alarm control panel (FACP) or mass notification system with 25V or 70V speaker circuits and a supervised NAC circuit (16-33 VDC) for strobe power. Consult the compatibility list in the spec sheet for verified FACP pairings.
Specifications
| SKU | KD-GCSVWA-A |
|---|---|
| Brand | Kidde Commercial |
| Form factor | Ceiling mount speaker-strobe |
| Speaker voltage | 25V/70V |
| Speaker power taps | 1/4W, 1/2W, 1W, 2W selectable |
| Sound output | Up to 90 dBA at 2W (reverberant, UL 1480) |
| Frequency response | 400-4,000 Hz |
| Strobe output (amber lens) | 13/26/65/82 cd, field-selectable |
| Strobe operating voltage | 16-33 VDC, 16-33 VFWR |
| Housing color | White |
| Lens color | Amber |
| Marking | ALERT (red) |
| Operating temp | 32°F to 122°F (0°C to 50°C) |
| Humidity | 0-93% noncondensing |
| Wire size | 12-18 AWG |
| Compatible electrical boxes | 4-inch square with plaster ring, 2-gang box |
| Compliance | UL 1638, UL 1971 (Mass Notification), ULC, CSFM, FM Approved, ADA |