- Fast shipping from four branches
- 30-day returns on unopened products
The FX-270 brings the familiar die-cast metal teardrop pull station into an intelligent FX-64/FX-1000 system, keeping the rugged, traditional feel building occupants already recognize while adding onboard addressing and diagnostics.
Built for the commercial fire installer
A single action pulls the handle to break the glass rod and latch an alarm at the control panel - no lift-door second step required. An integral microprocessor makes the alarm decision at the station itself rather than waiting on the panel, so twisted or shielded loop wire isn't required even on upgrades from conventional systems. Rotary address wheels on the back set the device's SLC address in seconds, and a diagnostic LED flashes green for normal polling or red during an alarm condition.
Key features
- Single-action, break-glass operation, alarm latches until reset
- Sturdy die-cast metal body, traditional teardrop design
- Rotary address wheels - no software programming tool required
- Integral microprocessor - decisions made at the station, twisted/shielded wire not required
- Diagnostic LED: green flashes normal polling, red flashes alarm
- ADA compliant, rated for ambient temperatures up to 120°F
System requirements
Compatible with Kidde FX-64 and FX-1000 intelligent systems. Mounts to a North American 2-1/2 in. deep 1-gang box, or a 4 in. square box (1-1/2 in. deep) with 1-gang cover. Device address 01-64 (64-point SLC) or 01-125 (250-point control panel).
Specifications
| SKU | KD-FX-270 |
|---|---|
| Brand | Kidde Commercial |
| Form factor | Single-action pull station, die-cast metal, rotary addressed |
| Compatibility | Kidde FX-64 and FX-1000 intelligent systems |
| Operation | Break glass, normally-open dry contact, latching |
| Communication voltage | 20 V peak-to-peak max |
| Current | Standby 350 µA, activated 500 µA |
| Device address range | 01-64 (64-point SLC) or 01-125 (250-point control panel) |
| Wire size | 12, 14, 16, or 18 AWG (16/18 preferred) |
| Mounting | North American 2-1/2" deep 1-gang box, or 4" square box (1-1/2" deep) with 1-gang cover |
| Operating temp | 32°F to 120°F (0°C to 49°C) |