You save

Kidde | Genesis LED EG4 Wall Mount Horn-Strobe, 15-110 cd Selectable, White, FIRE Marking | EG4AVWF

No reviews yet Write a Review
SKU:
KD-EG4AVWF

The Kidde Genesis LED EG4 horn-strobe delivers both audible and visual notification from a single wall-mount device, cutting install time and NAC circuit load on commercial fire alarm jobs. Field-selectable candela settings (15, 30, 75, or 110 cd) and dual horn patterns (TC3 temporal or constant) let you configure at the device instead of stocking multiple SKUs.

Built for the commercial fire alarm installer

The EG4 runs on 16-33 VDC or 16-33 VFWR, compatible with most conventional and intelligent fire alarm panels. It mounts to standard 1-gang, 2-gang, 3.5-inch octagon, or 4-inch square electrical boxes - no proprietary backboxes required. Room side wiring plate (GP10) ships included, so wiring connections stay accessible after the device is installed. UL 1971 and UL 464 listed, with ULC-S525 and ULC-S526 for Canadian installs.

Key features

  • Field-selectable candela: 15, 30, 75, or 110 cd - set at install, no ordering variants
  • Dual horn patterns: TC3 temporal or constant tone, selectable at the device
  • Low current draw: LED strobe technology reduces NAC circuit loading, supports longer wire runs and more devices per circuit
  • Standard electrical box mounting: fits 1-gang, 2-gang, 3.5" octagon, and 4" square boxes
  • Room side wiring plate included: GP10 plate ships with the device for accessible wiring after install
  • Broad voltage range: 16-33 VDC or VFWR covers most panel NAC outputs without extra power supplies

Synchronization

Strobes synchronize with Kidde CC Series Signal Modules, Booster and Auxiliary Power Supplies, and Intelligent and Conventional Control Panels. Maximum loop resistance for sync: 20 ohms between any two devices.

Brand:
Kidde Commercial
Form factor:
Wall mount horn-strobe
Power input:
16-33 VDC or 16-33 VFWR
Sound output:
80-92 dBA (reverberant low to anechoic high)
Horn pattern:
TC3 temporal or constant (field-selectable)
Strobe output:
15, 30, 75, or 110 cd (field-selectable)
Flash rate:
1 fps (approx.)
Wire size:
12 to 18 AWG
Compatible boxes:
1-gang, 2-gang, 3.5" octagon, 4" square
Dimensions:
4.95 x 5.78 x 1.62 in (W x H x D)
Operating temp:
32°F to 122°F (0°C to 50°C)
Operating humidity:
0 to 93% noncondensing
Storage temp:
-40°F to 158°F (-40°C to 70°C)
Synchronization:
20Ī© max between any two devices; requires Kidde sync source
Color:
White
Marking:
FIRE
Listings:
UL 1971, UL 464, ULC-S525, ULC-S526
Included accessories:
Room side wiring plate (GP10)
What candela settings are available on the EG4AVWF?
The strobe output is field-selectable at 15, 30, 75, or 110 cd. Settings are configured at the device during installation - no need to order separate SKUs for different candela ratings.
What horn patterns does this device support?
The horn supports TC3 temporal (three-pulse evacuation pattern per NFPA 72) and constant tone. Both patterns are field-selectable at the device.
What electrical boxes does the EG4 mount to?
Standard 1-gang, 2-gang, 3.5-inch octagon, and 4-inch square electrical boxes. No proprietary backbox required.
What voltage does this device require?
Operating voltage is 16-33 VDC or 16-33 VFWR. Compatible with most conventional and intelligent fire alarm panel NAC circuits.
Does this synchronize with other notification appliances?
Yes. Strobes synchronize using Kidde CC Series Signal Modules, Booster and Auxiliary Power Supplies, or compatible Intelligent and Conventional Control Panels. Maximum loop resistance for sync is 20 ohms between any two devices.
Is the EG4 listed for use in Canada?
Yes. The EG4 series carries ULC-S525 and ULC-S526 listings in addition to UL 1971 and UL 464.

Spec Sheet