The Kidde Genesis LED EG1VRN is a compact wall-mount LED strobe built for commercial fire alarm notification circuits. Field-selectable 15, 30, or 75 cd output covers everything from small offices to open corridors, and the ultra-low current draw (24 mA DC at any setting) means fewer power supplies and lighter wire runs on the NAC circuit.
Built for the commercial installer
The EG1 mounts directly to standard 1-gang electrical boxes with no trim ring required, protruding just over an inch from the wall. Optional trim rings (EG1TR red, EG1TW white) cover oversized openings on 4-inch square and octagon boxes. LED technology is backwards compatible with legacy Xenon Genesis strobes - mix them on the same NAC circuit and in the same field of view without replacing existing devices. UL 1971, UL 1638, and UL 464 listed. ADA compliant. CSFM approved.
Key features
- Field-selectable 15, 30, or 75 cd output - change the setting under the cover without removing the device from the wall
- Ultra-low current draw (24 mA DC at all cd settings) - fewer power supplies, more devices per NAC circuit
- Backwards compatible with Xenon strobes - mix LED and Xenon Genesis devices on the same circuit
- Single-gang mount, 1-1/8 in. depth - fits standard boxes with no visible mounting screws
- Under-cover diagnostic test points for circuit verification without removing the device
- Quick-swap covers - change between FIRE marking and no-marking variants in the field without rewiring
Synchronization
Genesis LED strobes exceed UL synchronization requirements (within 10 ms over a two-hour period) when paired with Kidde CC Series Signal Modules, Booster and Auxiliary Power Supplies, or Intelligent and Conventional Control Panels. Maximum 20 ohm wire resistance between any two devices on the circuit.
Can Genesis LED EG1 strobes be mixed with legacy Xenon strobes on the same circuit?
What electrical boxes does the EG1 strobe fit?
How do I change the candela setting?
Does this strobe synchronize with other Genesis devices?
Can the cover marking be changed in the field?
Spec Sheet