The FX-2Wire bridges conventional two-wire smoke detectors onto a Kidde FX Series addressable SLC loop without swapping out existing detectors. It monitors the two-wire zone, regulates and supervises the 24 VDC detector power, and reports alarm or trouble conditions back to the FACP as a single addressable point.
Built for the fire alarm installer
Class A and Class B SLC wiring configurations are selectable via a slide switch on the module face, matching the job's requirements without panel-side reprogramming. The module supports two-wire alarm verification (configurable through front panel programming or the configuration utility) and recognizes CleanMe signals from compatible Kidde detectors, flagging contamination before nuisance alarms start. Rotary address switches set the SLC point address with a screwdriver - no programming tool needed. Fits standard North American 4" square boxes.
Key features
- Conventional detector retention: keeps existing two-wire smoke detectors in service when upgrading to an FX Series addressable panel
- Class A/B selectable: slide switch on the module front sets SLC wiring style - no panel programming change required
- CleanMe signal recognition: monitors detector contamination status from compatible Kidde detectors
- Rotary address switches: set the SLC device address (01-127 depending on panel) with a screwdriver
- Standard mounting: fits 4" square x 2-1/2" deep 2-gang box or standard 4" square box 1-1/2" deep
- Bicolor LED status: flashing green for normal, flashing red for active - visible confirmation at the device
System requirements
Requires a Kidde FX Series intelligent fire alarm control panel with available SLC capacity. The module draws input power from the panel (12.4 to 28.3 VDC) to power connected two-wire detectors. Do not mix normally open contact initiating devices with two-wire conventional smoke detectors when using alarm verification. Cannot be used on a device loop with isolator modules or isolator bases.