The Kidde Genesis High Fidelity Ceiling Speaker-Strobe delivers 520 Hz notification for sleeping areas on a single SLC run - no separate speaker amplifier, no extra conduit. Drop it on a standard 4" square or octagonal box, connect two wires, and the panel handles the rest.
Built for the commercial fire installer
NFPA 72 requires a 520 Hz low-frequency tone in sleeping areas for effective occupant waking. The Genesis High Fidelity line meets that requirement at the device level with a square wave output, eliminating the need for a separate low-frequency tone generator upstream. Field-selectable multi-candela amber strobe provides visual notification with output levels set on-site via DIP switches. Listed to UL 1638, UL 464, CSA C22.2 No. 205, ULC-S526, and ULC-S541.
Key features
- 520 Hz square wave tone meets NFPA 72 sleeping area requirements without an external tone generator
- Field-selectable multi-candela amber strobe with high cd output - set candela on-site, no re-ordering
- Four power taps (1/4W, 1/2W, 1W, 2W) on a 25 VRMS audio circuit for flexible sound output
- Mounts on standard 4" square or octagonal ceiling boxes - no special hardware
- Synchronizable strobe output for multi-device installations per ADA and code requirements
- White housing, unmarked - clean appearance for occupied spaces without FIRE/ALERT labeling
System requirements
Connects to any 25 VRMS fire alarm audio circuit via 12-18 AWG wiring. Operating voltage 16-33 VDC (regulated) or 16-33 VFWR for the strobe circuit. Compatible with standard fire alarm control panels providing supervised notification appliance circuits.
Why does this model produce a 520 Hz tone instead of a standard alarm tone?
What's the difference between standard and High Fidelity Genesis speaker-strobes?
Can I adjust the candela output in the field?
Does this require a separate speaker amplifier?
What back box does this mount to?
Spec Sheet