- Fast shipping from four branches
- 30-day returns on unopened products
The KI-COD is a dedicated addressable carbon monoxide detector for jobs where CO monitoring is required on its own SLC address, separate from heat or smoke detection. It reports directly to a Kidde intelligent fire alarm control panel and drops into the same KI-series bases already stocked for other detectors on the loop.
Built for the commercial fire installer
The CO sensor meets UL 2034 alarm thresholds (70 ppm at 60-240 minutes, 150 ppm at 10-50 minutes, 400 ppm at 4-15 minutes) and carries a 10-year service life from date of manufacture, with automatic end-of-life trouble reporting at the panel so replacement isn't guesswork. Standard, relay, isolator, and audible sounder bases all fit this detector, keeping retrofit jobs on existing wiring.
Key features
- UL 2034-compliant CO sensing with defined alarm thresholds at 70, 150, and 400 ppm
- 10-year CO sensor life with automatic end-of-life trouble reporting at the panel
- Drop-in base compatibility: standard (KI-SB), relay (KI-RB), isolator (KI-IB), and audible sounder (KI-ABDT/KI-ABLT) bases
- Compact addressable footprint for jobs that need CO monitoring without a full multisensor detector
System requirements
Requires a Kidde intelligent fire alarm control panel and a KI-series detector base (sold separately). Mounts to standard 1-gang, 3-1/2" or 4" octagon, and 4" square electrical boxes. For a local sounder, pair with a KI-ABDT or KI-ABLT base and an FX-T3T4 Temporal Pattern Generator.
Specifications
| SKU | KD-KI-COD |
|---|---|
| Brand | Kidde Commercial |
| Form factor | Intelligent CO-only detector head, ceiling mount |
| Power input | 15.20 to 19.95 VDC (from SLC loop) |
| Standby / alarm current | 51 µA standby / 68 µA alarm |
| CO detection (UL 2034) | 70 ppm at 60-240 min; 150 ppm at 10-50 min; 400 ppm at 4-15 min |
| CO sensor life | 10 years from date of manufacture, with automatic end-of-life trouble reporting |
| Compatible bases | KI-SB standard, KI-RB relay, KI-IB isolator, KI-ABDT/KI-ABLT audible sounder |
| Operating environment | 32°F to 120°F (0°C to 49°C), 0 to 90% RH noncondensing |
| Storage temp | -4°F to 140°F (-20°C to 60°C) |
| Construction | High-impact engineering polymer, white |
| Shipping weight | 0.4 lbs (0.16 kg) |
| Compliance | UL 2034, UL 2075, CAN/CSA 6.19 |