Kidde Commercial

Genesis LED G4 Wall Mount Mass Notification Speaker-Strobe, White, Blue Lens, UL 2572

SKU KD-G4SVWA-B

  • Fast shipping from four branches
  • 30-day returns on unopened products

The Genesis LED G4SVWA-B is a wall-mount speaker-strobe purpose-built for mass notification systems. Blue lens and factory-applied "ALERT" marking meet UL 2572 requirements out of the box - no field labeling, no guesswork on code compliance.

Built for the commercial installer

Selectable 25VRMS or 70VRMS speaker operation means one SKU covers both circuit types without swapping hardware. Multiple candela settings adjust at the device via DIP switches, so you dial in the output for each space rather than over-specifying every location on the job. Mounts on standard 2-gang or 4-inch square electrical boxes with a consistent strobe-to-box offset for ADA-compliant notification layouts.

Strobe synchronization works with Kidde CC Series Signal Modules, Booster and Auxiliary Power Supplies, and both Intelligent and Conventional Control Panels. High-efficiency LED technology keeps current draw low across the NAC circuit, letting you run more devices per loop.

Key features

  • UL 2572 and ULC-S576 listed for mass notification - no workarounds for code compliance in the U.S. or Canada
  • Selectable 25VRMS or 70VRMS speaker tap - matches existing amplifier circuits without additional hardware
  • High-efficiency LED strobe with multiple field-selectable candela settings
  • Mounts on standard 2-gang or 4-inch square box - minimum 1-1/2 in. deep
  • Synchronizable with Kidde CC Series modules for code-required temporal patterns
  • White housing, blue lens, "ALERT" marking - factory-applied for mass notification identification

System requirements

Requires the GRSW-10 Room Side Wiring Plate (ordered separately). Standard 2-gang or 4-inch square electrical box, minimum 1-1/2 in. deep. NFPA recommends mounting at 81 inches AFF. Compatible with Kidde CC Series Intelligent and Conventional fire alarm control panels.

Specifications

SKUKD-G4SVWA-B
BrandKidde Commercial
Form factorWall mount speaker-strobe, Genesis LED G4 Series
Strobe operating voltage16 to 33 VDC, 16 to 33 VFWR
Speaker operating voltage25VRMS or 70VRMS (field-selectable)
Speaker frequency response (UL rated)400 Hz to 4,000 Hz
Speaker frequency response (nominal)100 Hz to 11,000 Hz
Strobe flash rate1 fps (approx.)
Lens colorBlue
MarkingAlert
Housing colorWhite (RAL 9002)
Wire size12 to 18 AWG (0.75 to 2.50 mm²)
Dimensions4.95 x 5.78 x 1.62 in (12.57 x 14.68 x 4.11 cm) (W x H x D)
Compatible electrical boxes2-gang, 4-inch square (min. 1-1/2 in. deep)
Trim platesG4TR (Red), G4TW (White)
Operating temp32 to 122°F (0 to 50°C)
Operating humidity0 to 93% noncondensing
Storage temp-40 to 158°F (-40 to 70°C)
ComplianceUL 2572, UL 1638, ULC-S576, RoHS 2011/65/EU
SynchronizationKidde CC Series Signal Modules, Booster/Auxiliary Power Supplies, Intelligent and Conventional Control Panels

Documents and resources

FAQs

What electrical box does this mount on?
Standard 2-gang or 4-inch square box, minimum 1-1/2 in. (3.81 cm) deep. NFPA recommends mounting at 81 inches AFF for wall-mount notification appliances.
Does this work with both 25V and 70V speaker circuits?
Yes. The G4SVWA-B has a field-selectable 25VRMS or 70VRMS speaker tap, so it works with either amplifier circuit type without changing hardware.
Is this UL listed for mass notification?
Yes. UL 2572 listed for mass notification in the United States and ULC-S576 listed in Canada. The blue lens and "ALERT" marking are factory-applied.
What panels and modules synchronize the strobe?
Compatible with Kidde CC Series Signal Modules, Booster and Auxiliary Power Supplies, and both Intelligent and Conventional Control Panels for synchronized strobe operation.
Is the GRSW-10 wiring plate included?
No. The GRSW-10 Room Side Wiring Plate is required for installation and is ordered separately.
What candela settings are available?
Multiple candela settings are field-selectable via DIP switches on the device, allowing you to match the output to the room size and NFPA spacing requirements without stocking multiple SKUs.